Vertical Turbine Fire Pumps
Product Types
The pump is based on Patterson’s more than 50 years of vertical pump expertise. Utilising the latest design concepts and engineering technology, these pumps are ideal for firefighting.
These pumps offer the flexibility to be cascaded as required to meet specific pressure criteria and have customisable length and construction to suit the specific application. Furthermore, their vertically oriented design optimises the use of floor space, making them a practical choice where space is at a premium. The standard configuration consists of cast iron discharge head, flanged steel columns, alloy shaft and cast iron bronze plated bowls. Special metallurgies are available as options.
OPERATION INTERVALS OF VERTICAL TURBINE TYPE FIRE PUMPS |
Diesel Engine | Electric Motor |
1800 RPM at rated speed | 1500 RPM at rated speed |
Flow (GPM) | Pressure (PSI) | Flow (GPM) | Pressure (PSI) |
150 | 43-277 | ||
200 | 40-264 | ||
250 | 40-244 | ||
500 | 59-333 | 500 | 43-277 |
750 | 67-403 | 750 | 42-305 |
1000 | 80-440 | 1000 | 44-272 |
1250 | 78-403 | 1250 | 47-207 |
1500 | 70-247 | 1500 | 45-199 |
2000 | 64-281 | 2000 | 47-196 |
2500 | 67-280 | 2500 | 60-189 |
3000 | 55-285 | 3000 | 55-180 |
3500 | 107-271 | 3500 | 55-126 |
4000 | 78-233 | 4000 | 74-273 |
4500 | 115-177 | 4500 | 70-265 |
5000 | 108-160 | 5000 | 68-255 |
Note: Speeds/conditions may be limited in some areas due to the availability of listed diesel engines that meet emission requirements.
Note: All pump ratings shown are UL Listed and FM Approved.